Model 132-010 consists of Robocon Valve (Balem 130) and Pressure Reducing Pilot valve. It automatically reduces and maintains constant pre-set low pressure regardless of flow rate change and/or inlet pressure change.
Combining with accurately designed pilot valve and features of the Robocon Valve (BALEM 130), operates diaphragm in chamber caused by change downstream pressure controls opening of Basic Valve to maintain constant downstream pressure.
Double chamber structure minimizes the effect of the valve action due to turbulence in the valve and easy to install and maintain.
Item | Description |
1 | BALEM 130(Robocon Valve) |
2 | Pressure Reducing Pilot Valve |
3 | Needle & Strainer |
4 | Cock Valve |
5 | Flow Controller |
6 | Pressure Gauge |
Pressure reducing valve selection guide |
In case of no demand for immediate water supply in-between |
In case of several demands in-between (Occasional short supply of water occurs) |
In case of water supply in the systemized block |
If the supply pipeline is very long and the altitude difference is great, it is a most safe and effective way to install a pressure reducing valve(Model 132-010) in between.
|
If there are several and greater water demands at the lower part of the line, and therefore short supply of water is expected at the higher part of the line, and therefore suspension of water supply is expected at the higher part of the line, it is recommended to install a pressure reducing and sustaining valve(Model 132-030).
|
For the water supply in the area that has been systemized by blocks, it is a safe and effective way to install a Robosys Robocon valve(Model 130-010). The valve can be installed additionally on the existing system to ensure a stable and safe running of the line, which can be supported by Balem SCADA system when a control system is required.
|
Y-type Globe | Up-right Globe Type | Angle Type |
▼ Y-type Globe (mm)
Valve Size | 50 | 65 | 80 | 100 | 125 | 150 | 200 | 250 | 300 | 350 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 |
L | 230 | 290 | 310 | 350 | 375 | 480 | 600 | 610 | 700 | 730 | 910 | 1010 | 1200 | 1400 | 1480 | 1650 | 1800 |
H1 | 78 | 88 | 100 | 110 | 125 | 143 | 175 | 205 | 230 | 265 | 300 | 380 | 420 | 500 | 565 | 590 | 640 |
H2 | 188 | 211 | 236 | 270 | 313 | 353 | 461 | 519 | 615 | 629 | 753 | 893 | 1030 | 1255 | 1412 | 1461 | 1584 |
ØE | 135 | 154 | 180 | 220 | 260 | 305 | 380 | 455 | 545 | 545 | 705 | 794 | 934 | 1160 | 1215 | 1315 | 1400 |
Valve Size | 50 | 80 | 100 | 150 | 200 | 250 | 300 |
A | 238 | 305 | 381 | 508 | 645 | 756 | 864 |
B | 78 | 93 | 105 | 140 | 165 | 200 | 223 |
Cmax | 200 | 240 | 275 | 375 | 470 | 535 | 625 |
Dmax | 157 | 179 | 206 | 284 | 360 | 420 | 465 |
ØE | 140 | 165 | 208 | 326 | 408 | 497 | 562 |
F | 119 | 152 | 191 | 254 | 322 | 378 | 432 |
G | 83 | 102 | 127 | 152 | 203 | 219 | 349 |
Robocon Series | |||
Pattern & Size |
Up-right Globe / Angle Type
|
Y-Type Globe
|
|
50 ~ 300A
|
50 ~ 1000A
|
||
Operating Pressure | 10kgf/㎠, 16kgf/㎠, 20kgf/㎠, 25kgf/㎠, 30kgf/㎠ | ||
End Connection | According to Customer Request | ||
Media | Water, Oil - Temperature : 0℃ ~ 80℃ |
Components | Materials | ||
Standard | Optional | ||
50A~350A | 400A~1000A | ||
Body & Cover & Disc | Ductile Iron | Cast Steel | SSC 13 |
Diaphragm Washer | SS 400 | Cast Steel | SSC 13 |
Cover Plug & Bearing | SSC 13 | ||
Shaft & Seat | STS 304 | ||
Diaphragm | N.R / C.R/ N.B.R | ||
Disc Seal | N.R / C.R/ N.B.R |
Hotline đặt hàng